What does PAT testing involve?

A PAT test is a visual inspection of an appliance followed by a short set of electrical tests, done with a dedicated test instrument. The item is then labelled as a pass or a fail and the result is recorded.

The trade name for it is in-service inspection and testing of electrical equipment. The inspection half matters as much as the testing half. HSE says visual examination is essential, and also that some types of defect can only be found by testing.

Here is what happens, in the order it happens.

What happens during a PAT test?

For each appliance, the tester works through the same steps:

  1. Switch the item off and unplug it.
  2. Give it an ID number and add it to the equipment list, if it is not already on it.
  3. Work out whether it is earthed (Class I) or double insulated (Class II).
  4. Inspect the plug, fuse, lead and casing.
  5. Connect it to the PAT tester and run the tests that suit its class.
  6. Check that it works as it should.
  7. Fix a pass or fail label to it and record the results.

At the end of the visit, anything that failed is pointed out to whoever is in charge. The certificate and results follow by email.

What is checked in the PAT testing visual inspection?

The inspection starts at the plug and works along the lead to the appliance itself.

The plug

  • Cracks, burn marks or bent pins
  • The fuse, which should be a proper fuse of a suitable rating for the appliance
  • Wires attached to the correct terminals, with the terminal screws tight
  • The cord grip holding the outer sheath of the cable, not the coloured inner wires
  • No bare wire showing other than at the terminals

On a moulded plug that cannot be opened, HSE notes that only the fuse can be checked.

The lead

  • Cuts, fraying or heavy scuffing
  • Tape repairs or joints
  • Signs it has been crushed, stretched or overheated

The appliance

  • A cracked or damaged casing, loose parts or missing screws
  • Signs of overheating, or of water getting in
  • Blocked vents and damaged switches

The tester also looks at how the item is being used. Is it suitable for the job and for the place it is used in? Are extension leads plugged into other extension leads, or adaptors overloaded? Is a lead trapped under furniture or run under a carpet?

HSE's guidance for low-risk workplaces makes the point that in some cases a user check and visual inspection is enough on its own. It is the inspection that finds the cracked plug and the taped-up lead.

What electrical tests are done in a PAT test?

The tests depend on how the appliance is built. These are the main ones.

TestWhat it checksApplies to
Earth continuityThat exposed metal parts are properly connected to the earth pin of the plugClass I (earthed)
Insulation resistanceThat the insulation between the live parts and the casing or earth is soundClass I and Class II
Protective conductor or touch currentHow much current leaks to earth or to the casing with the item running, used as well as or in place of an insulation testUsed where it suits the equipment
PolarityThat live, neutral and earth are wired to the right pins at both endsExtension leads and detachable power leads
Functional checkThat the item switches on and works normallyAll items

Extension leads and adaptors with a built-in RCD can also have the RCD trip tested.

The tester picks the right tests for each item. Some IT and electronic equipment needs a gentler choice of test than a kettle or a heater does, which is one reason HSE says the person testing must know how to use the equipment and how to interpret the results.

What is the difference between testing Class 1 and Class 2 appliances?

Class I appliances are earthed. If a fault makes the metal casing live, the earth wire carries the fault current away and the fuse or breaker cuts the supply. That only works if the earth connection is sound, and you cannot see that by looking. So the earth continuity test is the key one for Class I items such as kettles, toasters, fridges and many power tools.

Class II appliances are double insulated. They have extra insulation in place of an earth connection and carry a symbol of one square inside another. There is no earth to test, so the visual inspection of the casing matters most. HSE says that if you cannot see the double insulated symbol, you should assume the item is Class I.

There is more on telling them apart in Class 1 vs Class 2 appliances.

What equipment is included in PAT testing?

In short, anything that connects to the mains with a plug and can be moved. HSE's list includes:

  • Kettles, toasters, microwaves, fridges and other kitchen equipment
  • Vacuum cleaners and floor polishers
  • Computers, monitors, printers and photocopiers
  • Portable heaters, fans and lamps
  • Power tools
  • Extension leads, multi-way adaptors and detachable power leads
  • Mains chargers for phones, laptops and battery tools

Battery-operated equipment itself is not included, only the charger that plugs into the mains.

Large items that are wired into the building, such as a water boiler, are not portable appliances. HSE says they come under maintenance of the fixed installation instead.

Does PAT testing mean switching everything off?

Each item, yes, but not the whole building. An appliance has to be unplugged to be inspected and tested, so it is out of use for a few minutes.

For most equipment that is no trouble. Computers, tills, servers and phone systems need more planning, because they have to be shut down properly first.

To keep disruption down:

  • Tell staff the date, and ask them to save their work and shut down when asked
  • Decide in advance what cannot be switched off during working hours
  • Have someone on site who can unlock rooms and cupboards
  • Gather loose items such as spare leads, chargers and heaters in one place

Many businesses avoid the problem by booking an evening or weekend visit, which we offer.

How long the whole visit takes depends on the number of items and how easy they are to reach. See how long PAT testing takes.

What do you get after a PAT test?

HSE says labels and records are not a legal requirement, but that they are useful for managing your maintenance and for showing it is being done. In practice, the paperwork is what your insurer, licensing officer or landlord will ask to see.

With every job we do, you get:

  • A pass or fail label on each item, with an ID number and a retest date
  • A certificate by email
  • A results PDF listing every item and its results
  • A reminder when the retest is due

One limit is worth knowing. HSE says a portable appliance test can only show that an appliance was safe at the time of the test. Staff should still look over leads and plugs before use.

If an appliance fails

A failed item is labelled as failed and taken out of use, and we explain what is wrong with it. HSE's guidance is that faulty equipment should be removed from use without delay and then either repaired by someone competent or disposed of.

Repairs are not part of the test or the test price. You decide whether the item is worth repairing or should be replaced.

Our guide to what happens if an appliance fails a PAT test explains the common reasons and your options.

Who can carry out a PAT test?

HSE says a portable appliance test does not have to be done by an electrician. It does say that testing needs more knowledge and experience than inspection alone, the right equipment, and the ability to interpret the results.

Our testing is carried out by a qualified electrician. We cover Dundee, Broughty Ferry, Monifieth, Carnoustie, Invergowrie, Newport-on-Tay, Tayport and nearby.

You can read more about our PAT testing in Dundee service, check the price list, which starts at £74.99 for up to 30 items with no VAT to add, or ask for a fixed price. You can also call 01382 721486.

Sources

More PAT testing questions

Call Get a price