What is the difference between Class 1 and Class 2 appliances?

A Class 1 appliance protects you with an earth connection. A Class 2 appliance protects you with a second layer of insulation and has no earth.

That one difference decides how the appliance is built, what the rating plate shows, and which tests it gets during a PAT test.

You will see the classes written both ways. The standards use Roman numerals (Class I and Class II). Most people type Class 1 and Class 2. They mean the same thing.

What is a Class 1 appliance?

A Class 1 appliance has basic insulation around its live parts and an earth wire connected to its exposed metal parts.

If the insulation fails and a live wire touches the metal case, the fault current flows down the earth wire instead of through the next person who touches it. That current blows the fuse or trips the circuit breaker, and the appliance goes dead.

The protection only works if the earth path is complete, from the metal case, through the flex, the plug and the socket, back to the building's earthing. A broken earth wire inside a flex gives no warning. The appliance carries on working normally until the day something goes wrong.

HSE puts it simply: if there is a fault inside Class 1 equipment, the outside of it could give an electric shock if the earth connection is not there.

Common Class 1 items:

  • Kettles, toasters and microwaves
  • Fridges, freezers, washing machines and dishwashers
  • Irons and many floor cleaners
  • Most desktop computers and some monitors
  • Extension leads and detachable mains leads with three cores

What is a Class 2 appliance?

A Class 2 appliance is double insulated. It has the basic insulation plus a second, supplementary layer, or one reinforced layer that does the job of both.

The idea is that a single fault cannot make any part you can touch live. HSE describes it as extra insulation within the construction of the equipment to prevent accidental contact with live parts, even if there is a fault.

Because the safety comes from the insulation, a Class 2 appliance does not need an earth connection. Its flex normally has two cores, live and neutral.

Common Class 2 items:

  • Phone and laptop chargers
  • Hairdryers and electric shavers
  • Many power tools, such as drills and sanders
  • Most televisions, radios and table lamps
  • Many desk fans and vacuum cleaners

A plastic case does not make something Class 2 by itself. Some plastic-bodied kettles are earthed because of the metal element inside. The rating plate is what counts.

What is the difference between Class 1 and Class 2 appliances?

Class 1Class 2
How it protects youBasic insulation plus an earth connectionDouble or reinforced insulation
Earth wireYes, connected to exposed metalNo protective earth
FlexThree coresUsually two cores
SymbolOften none, sometimes an earth symbolA square inside a square
What it depends onThe earth path staying intactThe casing and insulation staying intact
Main PAT testsEarth continuity and insulation resistanceInsulation resistance, no earth continuity test
Typical examplesKettle, toaster, fridge, extension leadPhone charger, hairdryer, drill, lamp

How do I tell if an appliance is Class 1 or Class 2?

Look at the rating plate. This is the label or moulded panel that shows the voltage, wattage and model number. It is usually on the back or underside.

  • A square inside a square means Class 2, double insulated. On small chargers it is often moulded into the plastic with no ink, so use a torch.
  • No such symbol means you should treat it as Class 1. HSE's guidance says exactly this: if you cannot see the symbol, assume the item is Class 1.

Other clues help, but none of them is proof:

  • The plug's earth pin. A plastic earth pin on a moulded plug means there is no earth connection, so the item is not Class 1. A metal earth pin tells you nothing either way, because all standard UK plugs have one.
  • The flex. A thin, flat two-core flex points to Class 2. A three-core flex points to Class 1.
  • Exposed metal. Bare metal you can touch on a mains appliance usually means it is earthed.

When a tester cannot confirm the class, the safe course is to test the item as Class 1 and look more closely if it will not pass.

How is a Class 1 appliance PAT tested?

Every item starts with a visual inspection. The tester checks the plug, fuse, flex, cord grip and casing for damage, overheating and wrong fuses. Many faults are found at this stage without an instrument.

A Class 1 appliance then gets two main electrical tests:

  1. Earth continuity. The tester passes a current between the earth pin of the plug and the exposed metal of the appliance, and measures the resistance. A low reading shows the earth path is sound. A high reading, or none, means the earth is broken or poorly connected.
  2. Insulation resistance. The tester checks that the live conductors are properly insulated from the earthed metalwork.

Where it is safe and sensible to do so, a functional check follows to confirm the appliance works.

The full process is set out in what PAT testing involves.

How is a Class 2 appliance PAT tested?

A Class 2 appliance has no protective earth, so there is nothing to run an earth continuity test on. It gets the same visual inspection, which matters more here because the casing is the protection. A cracked case, a missing cover or a split flex is a fail.

After that it gets an insulation test. The tester checks the insulation between the live conductors and the outside of the appliance, using a probe on any metal parts that can be touched.

It is worth knowing what HSE says about low-risk places such as offices and shops. Its leaflet INDG236 says Class 2 equipment will not need a portable appliance test there, as long as user checks and visual inspections are carried out. The current IET Code of Practice takes a similar line, that a visual inspection may be enough for some Class 2 items.

In practice, when we are on site with a tester, the insulation test on a Class 2 item takes seconds, so we do the inspection and the test and record both.

Do Class 2 appliances need PAT testing as often as Class 1?

Usually not. HSE's suggested starting intervals for low-risk environments are:

EquipmentFormal visual inspectionCombined inspection and test
Class 1, such as kettles and ironsEvery 6 months to 1 yearEvery 1 to 2 years
Class 2, hand-heldEvery 6 months to 1 yearNot needed
Class 2, not hand-held, such as fans and lampsEvery 2 to 4 yearsNot needed

These are suggestions for offices, shops and similar places. Equipment in workshops, kitchens and on building sites has a harder life and needs looking at more often, whatever its class.

The right interval comes from your own risk assessment, not from a fixed rule. We go through that in how often should PAT testing be done.

Do I need to know the class before booking a PAT test?

No. Working out the class of each item is part of the job, and it is recorded on your results.

For a rough count, include everything with a plug, plus extension leads and detachable mains leads. A laptop charger counts, the laptop does not. Our price list starts at £74.99 for 1 to 30 items, with no VAT to add and no call-out charge in Dundee.

We carry out PAT testing in Dundee and nearby, including Broughty Ferry, Monifieth, Carnoustie, Invergowrie, Newport-on-Tay and Tayport. Each item gets a pass or fail label with an ID number and retest date, and you get a certificate and a results PDF by email.

To find out what your premises would cost, ask for a price or phone 01382 721486.