How often should PAT testing be done?

There is no set legal interval. UK law does not say how often PAT testing must be done, and HSE is clear that there is no requirement to test everything every year.

How often depends on what the equipment is, how it is built, who uses it and where. A drill on a building site might need testing every three months. A desktop computer in an office might need a test every five years, or none at all if it is double insulated.

HSE publishes suggested starting intervals, which are set out below.

Is there a legal requirement for how often PAT testing is done?

No. The Electricity at Work Regulations 1989 require equipment to be maintained so that it does not cause danger. HSE's guidance says the law does not say how you must do this or how often.

HSE's answer to "Must I test appliances every year by law?" is no.

The two main exceptions are in Scotland. Private landlords must have an electrical safety inspection, including the appliances they supply, at least every five years. Short-term let licences also carry a five-year maximum. Both are covered further down.

For everyone else, the legal position is covered in is PAT testing a legal requirement.

How often should PAT testing be done in an office or shop?

HSE's leaflet for low-risk workplaces, INDG236, gives suggested initial intervals. They are starting points, not rules.

EquipmentUser checksFormal visual inspectionInspection and test
Battery-operated equipment (under 40 volts)NoNoNo
Desktop computers and screensNoEvery 2 to 4 yearsNot if double insulated, otherwise up to 5 years
Photocopiers and fax machines, rarely movedNoEvery 2 to 4 yearsNot if double insulated, otherwise up to 5 years
Double insulated equipment, not hand-held, such as fans and table lampsNoEvery 2 to 4 yearsNo
Double insulated hand-held equipment, such as some floor cleanersYesEvery 6 months to 1 yearNo
Earthed equipment, such as kettles, irons and some floor cleanersYesEvery 6 months to 1 yearEvery 1 to 2 years
Leads, plugs, extension leads and battery chargersYesEvery 6 months to 4 yearsEvery 1 to 5 years

Three things stand out.

First, earthed equipment that gets handled and moved, such as kettles, is the group HSE suggests testing most often.

Second, HSE says double insulated equipment does not need a portable appliance test, though it still needs visual inspection. Our guide to Class 1 and Class 2 appliances explains how to tell them apart.

Third, extension leads and detachable power leads are items in their own right, and their interval follows the equipment they are used with.

How often should PAT testing be done on construction sites and in workshops?

Much more often. Equipment gets knocked about, used outdoors and dragged across rough ground.

HSE's fuller guidance, HSG107, suggests these initial intervals:

Type of workUser checksFormal visual inspectionInspection and test
Construction, 110V equipmentWeeklyMonthlyBefore first use on site, then every 3 months
Construction, 230V equipmentDaily or every shiftWeeklyBefore first use on site, then monthly
Construction site officesMonthlyEvery 6 monthsBefore first use on site, then yearly
Heavy industrial or high risk of damageDailyWeeklyEvery 6 to 12 months
Light industrialYesBefore first use, then every 6 monthsEvery 6 to 12 months
Equipment hireNot applicableBefore issue and after returnBefore issue

HSG107 states that these suggested frequencies are not legal requirements. Main contractors and site managers often set their own rules on top, so check what your site requires.

Does PAT testing have to be done every year?

No, though for a lot of equipment a year is a sensible interval.

Annual testing became a habit because it is simple to run. One visit a year, everything tested, one date in the diary. For kettles, heaters, kitchen equipment, vacuum cleaners and extension leads in a busy workplace, that fits well with HSE's suggested 1 to 2 years.

For low-risk items, a yearly test is more than HSE suggests. HSE reviewed its own offices in 2011 and, after looking at five years of annual results, stopped testing some equipment and relied on user checks and visual inspections instead.

HSE also gives a practical tip. If you group equipment together to be tested in one visit, use the shortest interval in the group, not the longest. Or split your equipment into groups by interval.

What decides how often an appliance needs testing?

These are the things worth weighing up:

  • Where it is used. A kitchen, workshop or building site is harder on equipment than an office.
  • How it is built. Earthed equipment relies on its earth connection, which can only be confirmed by testing.
  • How it is used. Hand-held and frequently moved equipment gets damaged more often than equipment that sits still.
  • Who uses it. Equipment used by the public, guests or tenants needs closer attention than equipment used by trained staff. HSG107 says equipment for public use may need much more frequent visual inspection.
  • Age and history. Older equipment and equipment that has failed before deserves a shorter interval.
  • Past results. HSG107 says a low failure rate suggests the interval can be lengthened, and a high failure rate suggests it should be shortened.

The IET Code of Practice for In-Service Inspection and Testing of Electrical Equipment, which testers work to, takes the same approach. Earlier editions had a table of suggested intervals that was widely treated as a set of fixed rules. The fifth edition in 2020 removed it and asks for intervals to be decided by risk assessment.

How often do landlords need PAT testing in Scotland?

Private landlords in Scotland must have an electrical safety inspection before a tenancy starts and then at intervals of no more than five years. Under the Scottish Government's Repairing Standard guidance, that inspection covers both the fixed wiring and the appliances the landlord has supplied.

The same guidance notes that retest dates for appliances will usually be more frequent than five years. Many landlords have appliances checked every year or two, or at each change of tenant.

Short-term let licences require inspection at least every five years, or more often if the competent person carrying it out directs. Individual councils may add their own conditions, so check your licence.

Rules for landlords in the rest of the UK are different. Our guide to PAT testing for landlords in Scotland has the detail.

Who decides when the next PAT test is due?

You do, as the person responsible for the equipment. HSE's guidance says the decision on when the next test is due should be made by the dutyholder on a risk assessment basis.

A tester can advise, and should. We put a retest date on each label and send a reminder when it is due, based on the equipment and how it is used. If your own risk assessment, your insurer or your licence points to a different interval, tell us and we will work to that.

What checks should be done between PAT tests?

A test only shows that an item was safe on the day. HSE says user checks should carry on after testing for that reason.

Before using equipment, with it unplugged, staff should look for:

  • Cuts, fraying or heavy scuffing on the lead
  • A cracked plug or bent pins
  • Tape wrapped round a lead or joining two leads
  • Coloured wires showing where the lead enters the plug
  • Burn marks or staining on the plug, lead or casing
  • Loose parts, missing screws or a damaged case

Anything that looks wrong should be taken out of use until it has been checked. It costs nothing and it catches most faults.

If you would like a sensible testing schedule set up for your equipment, we carry out PAT testing in Dundee and nearby towns, including evenings and weekends. Prices start at £74.99 for up to 30 items and the full price list is online. To book, ask for a price or call 01382 721486.

Sources